| Input parameters |
| Rated power, VA/W |
8000 / 8000 |
| Voltage range |
100~280V (single phase, 2 wires plus ground) |
| Voltage range |
100~175V with linear derating at 50~100% load |
| Frequency |
40~70Hz |
| Power factor |
> 0.99 (at full load) |
| Current harmonic distortion factor |
< 3% |
| Input connections |
Input terminal block x 1 |
| output parameters |
| Power factor |
1 |
| Voltage |
200, 208, 220, 230, 240 VAC current (single phase) |
| Frequency |
50/60Hz±0.05Hz |
| Voltage THD |
< 2% (with linear load) |
| Overload capacity |
≤ 105%: continuous operation 106 ~ 125%: 5 min. 126 ~ 150%: 1 min. > 150%: 500ms |
| conclusions |
IEC C13 x 6 (non-managed) IEC C19 x 4 (non-managed) Terminal block x 1 (non-managed) IEC C19 x 1 (managed) |
| efficiency |
| Normal mode |
up to 95.5% |
| Economy mode |
up to 99% |
| Rechargeable batteries |
| Battery capacity |
20×9 Ah |
| Battery voltage |
240 V DC current |
| Charging current |
1.5 A (default) 8 A (maximum) |
| Common parameters |
| Noise level |
50 dB |
| Display |
Graphic LCD display with multilingual interface |
| Communication interfaces |
1 MINI slot, 1 USB port, 1 RS232 port, 1 RS485 port, 1 REPO/ROO port, 4 dry contacts |
| Dimensions (W × D × H), mm |
440×750×218 |
| Weight, kg |
85.5 |
| Ambient operating temperature |
0~55°C |
| Relative humidity of the environment |
5 ~ 95% (non-condensing) |